Thermostatic Mixing Valve Troubleshooting

Symptom Probable Cause Remedy
The desired mixed water temp. cannot be obtained or valve is difficult to set. Hot and cold suppliers are reversed, valve is full of debris, or strainers are fouled Refit valve so H &C are correct, flush valve with water, and clean strainers
Mix temperature is unstable Strainers are fouled or fluctuating supply pressure Clean strainers and install pressure reducing valve's on H & C inlet supplies.
Mix temperature changing over time Fluctuating supply pressures or strainers are full. Install pressure reducing valves and clean strainers.
Either full hot or cold water flowing Valve is set incorrectly Adjust mix. Temperature to 95° F-131° F
No flow from the valve outlet. Hot or cold water supply failure or strainers are fouled Restore inlet supply & check mix. Temperature and clean strainers
Flow rate reduced or fluctuating Valve or inlet fitting fouled by debris. Check valve and inlet fittings for blockage.
Mixed water temp. too hot or cold. Valve has been tampered with, valve incorrectly set, or inlet temperatures are not within specified limits. Re-adjust to required set temperature to ensure inlet temperatures are within specified limits.
Mixed water temperature does not change when the temperature adjuster is moved. Hot and cold supplies are reversed. Refit the valve to the correct hot and cold configurations.
Hot water flows into the cold water system or vise versa. Valve is fouled. Clean strainers and remove debris.
Valve is noisy. Water velocity is too high. Reduce water velocity.

Click below for installation and maintenance sheets:

ZW1017 Installation and Maintenance sheet
ZW1017HT Installation and Maintenance sheet
ZW1017MM Installation and Maintenance sheet
ZW1070 Installation and Maintenance sheet